模块化三进三出系列
3-2-1、(10-200KVA)空开配置
功率 | 电池 电压 | 输入电流A | 输出电流A | 电池电流A | 输入空开A | 输出空开A | 电池空开A |
10KVA | 768VDC | 16 | 15 | 13 | 25/3P | 16/3P | 16/3P |
20KVA | 768VDC | 32 | 30 | 25 | 63/3P | 32/3P | 25/3P |
30KVA | 768VDC | 48 | 45 | 38 | 63/3P | 63/3P | 63/3P |
40KVA | 768VDC | 64 | 61 | 50 | 100/3P | 63/3P | 63/3P |
50KVA | 768VDC | 80 | 76 | 63 | 100/3P | 100/3P | 63/3P |
60KVA | 768VDC | 96 | 91 | 75 | 100/3P | 100/3P | 100/3P |
70KVA | 768VDC | 112 | 106 | 88 | 125/3P | 125/3P | 100/3P |
80KVA | 768VDC | 128 | 121 | 100 | 160/3P | 125/3P | 125/3P |
90KVA | 768VDC | 144 | 136 | 113 | 160/3P | 160/3P | 125/3P |
100KVA | 768VDC | 159 | 151 | 125 | 160/3P | 160/3P | 125/3P |
110KVA | 768VDC | 175 | 167 | 138 | 200/3P | 160/3P | 160/3P |
120KVA | 768VDC | 191 | 182 | 150 | 200/3P | 200/3P | 160/3P |
130KVA | 768VDC | 207 | 197 | 163 | 250/3P | 200/3P | 160/3P |
140KVA | 768VDC | 223 | 212 | 175 | 250/3P | 250/3P | 200/3P |
150KVA | 768VDC | 239 | 227 | 188 | 250/3P | 250/3P | 200/3P |
160KVA | 768VDC | 255 | 242 | 201 | 250/3P | 250/3P | 200/3P |
170KVA | 768VDC | 271 | 258 | 213 | 320/3P | 250/3P | 250/3P |
180KVA | 768VDC | 287 | 273 | 226 | 320/3P | 320/3P | 250/3P |
190KVA | 768VDC | 303 | 288 | 238 | 320/3P | 320/3P | 250/3P |
200KVA | 768VDC | 319 | 303 | 251 | 320/3P | 320/3P | 250/3P |
注:
l 实际开关容量不得小于表中开关容量;
l 电池开关额定工作直流电压,不得低于768VDC。
3-2-2、(10-200KVA)电缆配置
功率 | 输入电缆mm2 | 输出电缆mm2 | 电池电缆mm2 | 零线 mm2 | 地线 mm2 | 备注 |
10KVA | 6 | 6 | 6 | 6 | 6 | |
20KVA | 10 | 10 | 10 | 10 | 6 | |
30KVA | 10 | 10 | 10 | 10 | 6 | |
40KVA | 16 | 16 | 16 | 16 | 10 | |
50KVA | 25 | 25 | 16 | 25 | 10 | |
60KVA | 25 | 25 | 25 | 25 | 10 | |
70KVA | 25 | 25 | 25 | 25 | 10 | |
80KVA | 35 | 35 | 25 | 35 | 16 | |
90KVA | 35 | 35 | 35 | 35 | 16 | |
100KVA | 50 | 50 | 50 | 50 | 25 | |
110KVA | 50 | 50 | 50 | 50 | 25 | |
120KVA | 70 | 70 | 50 | 70 | 35 | |
130KVA | 70 | 70 | 70 | 70 | 35 | |
140KVA | 70 | 70 | 70 | 70 | 35 | |
150KVA | 70 | 70 | 70 | 70 | 35 | |
160KVA | 70 | 70 | 70 | 70 | 35 | |
170KVA | 95 | 95 | 70 | 95 | 35 | |
180KVA | 95 | 95 | 95 | 95 | 35 | |
190KVA | 95 | 95 | 95 | 95 | 35 | |
200KVA | 95 | 95 | 95 | 95 | 35 |
注:
l 实际电缆线径不得小于表中线径;
l电缆的截面积是按铜芯电缆计算的(如果用铝芯电缆则需增加30%)同时考虑了温度的上升以及最多15米(交流回路)或10米(直流回路)的线路压降。如果线路更长,则要选用截面积更大的电缆(具体可向技术支持部咨询),以保证线路的压降低于3%(交流)或1%(直流);
特别说明:考虑到日后扩容的方面,模块化UPS的线缆、空开配置,一般按机柜最大功率配置。